API 1080 G & 1090 G Series DC Input Alarms
API 1080 G & 1090 G Series DC Input Alarms
The API 1080 G and API 1090 G accept a DC voltage or current input and provide visual alarm indication and alarm relay contact outputs. Voltage and current input ranges can be field-configured via external rotary and slide switches. Offset ranges such as 1-5 VDC and 4-20 mADC are also included. Heavy-duty relay contacts allow the module to directly control high capacity loads. Top-accessible potentiometers are used to adjust the alarm setpoint from 0 to 100% and the deadband from 1 to 100%.
The API 1080 G provides a single setpoint adjustment of the two DPST relay contacts. The alarm output can be field configured for HI or LO operation, latching or non-latching, and normal or reverse acting. The deadband and alarm setpoint are adjustable.
The API 1090 G provides two setpoint adjustments of the two SPDT relay contacts. The alarm outputs can be configured in the field for HI/HI, LO/LO, HI/LO or LO/HI operation, latching or non-latching, and normal or reverse acting. Deadband and alarm setpoints are independently adjustable for each alarm.
Base Model # | Power | Description | Socket | Approvals | Normally In Stock | Configure Part # |
API 1080 G | 115 VAC | DC input single alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1080 G A230 | 230 VAC | DC input single alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1080 G D | 9-30 VDC | DC input single alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1080 G P | 85-265 VAC, 60-300 VDC | DC input single alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1090 G | 115 VAC | DC input dual alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1090 G A230 | 230 VAC | DC input dual alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1090 G D | 9-30 VDC | DC input dual alarm. Isolated input. | API 011 or API 011 FS | None | Inquire | |
API 1090 G P | 85-265 VAC, 60-300 VDC | DC input dual alarm. Isolated input. | API 011 or API 011 FS | None | Inquire |